Soft starters
We also offer soft starters for medium voltages up to 13.5 kV.
Here is the data sheet (PDF download). Please ask us for this device separately.
The soft starter VersiStart II [3,5 – 16 A] enables controlled, gentle start-up of asynchronous motors and significantly reduces mechanical and electrical loads. The device works microcontroller-controlled, compact and reliable – ideal for pumps, fans and conveyor technology. Thanks to its easy installation on the 35 mm standard rail, the VersiStart II is a cost-effective alternative to the classic star triangle switch.
Characteristics
- Two-phase soft starter
- Microcontroller controlled
- Optimized soft start with current and torque reduction
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization over three potentiometers
- No additional control voltage required (standard)
- no network center conductor (N) required
- compact design, only 45 mm
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operating condition, bridging and failure (optional)
Options
- Special voltages 230 V / 480 V
- Wide Voltage 200 – 480 V with external control voltage 24 V DC (option B)
- Bypass and failure reporting contacts (option I)
- Engine PTC monitoring (option I)
- Current control function (200 – 500 % × I)N) (Option I)
- Cooling unit temperature monitoring (option I)
- √3-Schaltung for power optimization (Option I)
- Reporting contact ‘Soft start to soft exit’ (option M)
Technical data (excerpt)
- Operating voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 3,5 A / 6,5 A / 12 A / 16 A
- Engine power at 400 V: 1,5 – 7,5 kW
- Start-up time 0,5 – 10 s | Expiration time 0,25 – 10 s
- Starting voltage 40 – 80 %
- Relay outputs switching power: 2 A / 250 VAC / 30 VDC
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 0,4 kg
Preferred areas of application
- Door and door drives
- Pumps, fans and fans
- Conveying and packaging equipment
- Transportation equipment, assembly lines and mechanical engineering
Note:
When using IE3-Motoren, higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices each have a higher power level.
The soft starter VersiStart II [3,5 – 16 A] enables controlled, gentle start-up of asynchronous motors and significantly reduces mechanical and electrical loads. The device works microcontroller-controlled, compact and reliable – ideal for pumps, fans and conveyor technology. Thanks to its easy installation on the 35 mm standard rail, the VersiStart II is a cost-effective alternative to the classic star triangle switch.
Characteristics
- Two-phase soft starter
- Microcontroller controlled
- Optimized soft start with current and torque reduction
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization over three potentiometers
- No additional control voltage required (standard)
- no network center conductor (N) required
- compact design, only 45 mm
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operating condition, bridging and failure (optional)
Options
- Special voltages 230 V / 480 V
- Wide Voltage 200 – 480 V with external control voltage 24 V DC (option B)
- Bypass and failure reporting contacts (option I)
- Engine PTC monitoring (option I)
- Current control function (200 – 500 % × I)N) (Option I)
- Cooling unit temperature monitoring (option I)
- √3-Schaltung for power optimization (Option I)
- Reporting contact ‘Soft start to soft exit’ (option M)
Technical data (excerpt)
- Operating voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 3,5 A / 6,5 A / 12 A / 16 A
- Engine power at 400 V: 1,5 – 7,5 kW
- Start-up time 0,5 – 10 s | Expiration time 0,25 – 10 s
- Starting voltage 40 – 80 %
- Relay outputs switching power: 2 A / 250 VAC / 30 VDC
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 0,4 kg
Preferred areas of application
- Door and door drives
- Pumps, fans and fans
- Conveying and packaging equipment
- Transportation equipment, assembly lines and mechanical engineering
Note:
When using IE3-Motoren, higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices each have a higher power level.
The soft-starter VersiStart II [17 – 45 A] was developed for the controlled and low-wear start-up of three-phase induction motors. It reliably reduces starting current and torque, ensures a smooth run-up and thus extends the service life of the motor and drive. The device is microcontroller-controlled, compact and can be easily integrated into existing controllers thanks to pluggable power terminals.
Characteristics
- Two-phase controlled soft starter
- Microcontroller controlled
- Optimized soft start with torque reduction
- √3-Schaltung for more compact design
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization via three potentiometers (start-up time, start-up voltage, run-off time)
- No additional control voltage required
- no network center conductor (N) required
- spring-loaded terminals on the control side, power-side pluggable connections
- Cooling element temperature monitoring integrated
- Compact design: 45 mm to 32 A, 52,5 mm at 45 A
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operational mode, bridging and malfunction
Options
- Special voltages 230 V / 480 V
- Wide voltage 400–600 V with external control voltage 24 V DC (option B)
- Reporting contact (M): Start soft start to finish soft start
- Engine PTC monitoring (on request)
Technical data (excerpt)
- Mains voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 17 A / 25 A / 32 A / 45 A
- Engine power at 400 V: 7,5 – 22 kW
- Start-up time 0,5 – 10 s | Expiration time 0,5 – 10 s
- Starting voltage 40 – 80 %
- Relay output: 3 A / 250 VAC and 30 VDC
- Impact strength: 4 kV
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 1 kg
Preferred areas of application
- Electric pumps and vacuum pumps
- Fans and fans
- Drilling cranes and extraction equipment
- Stirrers, centrifuges, saws and conveyors
- Machinery for working wood and metal, and grinding machines
Note:
When using IE3-Motoren, the higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices should generally be dimensioned to a higher power level.
The soft-starter VersiStart II [17 – 45 A] was developed for the controlled and low-wear start-up of three-phase induction motors. It reliably reduces starting current and torque, ensures a smooth run-up and thus extends the service life of the motor and drive. The device is microcontroller-controlled, compact and can be easily integrated into existing controllers thanks to pluggable power terminals.
Characteristics
- Two-phase controlled soft starter
- Microcontroller controlled
- Optimized soft start with torque reduction
- √3-Schaltung for more compact design
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization via three potentiometers (start-up time, start-up voltage, run-off time)
- No additional control voltage required
- no network center conductor (N) required
- spring-loaded terminals on the control side, power-side pluggable connections
- Cooling element temperature monitoring integrated
- Compact design: 45 mm to 32 A, 52,5 mm at 45 A
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operational mode, bridging and malfunction
Options
- Special voltages 230 V / 480 V
- Wide voltage 400–600 V with external control voltage 24 V DC (option B)
- Reporting contact (M): Start soft start to finish soft start
- Engine PTC monitoring (on request)
Technical data (excerpt)
- Mains voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 17 A / 25 A / 32 A / 45 A
- Engine power at 400 V: 7,5 – 22 kW
- Start-up time 0,5 – 10 s | Expiration time 0,5 – 10 s
- Starting voltage 40 – 80 %
- Relay output: 3 A / 250 VAC and 30 VDC
- Impact strength: 4 kV
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 1 kg
Preferred areas of application
- Electric pumps and vacuum pumps
- Fans and fans
- Drilling cranes and extraction equipment
- Stirrers, centrifuges, saws and conveyors
- Machinery for working wood and metal, and grinding machines
Note:
When using IE3-Motoren, the higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices should generally be dimensioned to a higher power level.
The soft starter VersiStart II [3,5 – 16 A] enables controlled, gentle start-up of asynchronous motors and significantly reduces mechanical and electrical loads. The device works microcontroller-controlled, compact and reliable – ideal for pumps, fans and conveyor technology. Thanks to its easy installation on the 35 mm standard rail, the VersiStart II is a cost-effective alternative to the classic star triangle switch.
Characteristics
- Two-phase soft starter
- Microcontroller controlled
- Optimized soft start with current and torque reduction
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization over three potentiometers
- No additional control voltage required (standard)
- no network center conductor (N) required
- compact design, only 45 mm
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operating condition, bridging and failure (optional)
Options
- Special voltages 230 V / 480 V
- Wide Voltage 200 – 480 V with external control voltage 24 V DC (option B)
- Bypass and failure reporting contacts (option I)
- Engine PTC monitoring (option I)
- Current control function (200 – 500 % × I)N) (Option I)
- Cooling unit temperature monitoring (option I)
- √3-Schaltung for power optimization (Option I)
- Reporting contact ‘Soft start to soft exit’ (option M)
Technical data (excerpt)
- Operating voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 3,5 A / 6,5 A / 12 A / 16 A
- Engine power at 400 V: 1,5 – 7,5 kW
- Start-up time 0,5 – 10 s | Expiration time 0,25 – 10 s
- Starting voltage 40 – 80 %
- Relay outputs switching power: 2 A / 250 VAC / 30 VDC
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 0,4 kg
Preferred areas of application
- Door and door drives
- Pumps, fans and fans
- Conveying and packaging equipment
- Transportation equipment, assembly lines and mechanical engineering
Note:
When using IE3-Motoren, higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices each have a higher power level.
The soft-starter VersiStart II [17 – 45 A] was developed for the controlled and low-wear start-up of three-phase induction motors. It reliably reduces starting current and torque, ensures a smooth run-up and thus extends the service life of the motor and drive. The device is microcontroller-controlled, compact and can be easily integrated into existing controllers thanks to pluggable power terminals.
Characteristics
- Two-phase controlled soft starter
- Microcontroller controlled
- Optimized soft start with torque reduction
- √3-Schaltung for more compact design
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization via three potentiometers (start-up time, start-up voltage, run-off time)
- No additional control voltage required
- no network center conductor (N) required
- spring-loaded terminals on the control side, power-side pluggable connections
- Cooling element temperature monitoring integrated
- Compact design: 45 mm to 32 A, 52,5 mm at 45 A
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operational mode, bridging and malfunction
Options
- Special voltages 230 V / 480 V
- Wide voltage 400–600 V with external control voltage 24 V DC (option B)
- Reporting contact (M): Start soft start to finish soft start
- Engine PTC monitoring (on request)
Technical data (excerpt)
- Mains voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 17 A / 25 A / 32 A / 45 A
- Engine power at 400 V: 7,5 – 22 kW
- Start-up time 0,5 – 10 s | Expiration time 0,5 – 10 s
- Starting voltage 40 – 80 %
- Relay output: 3 A / 250 VAC and 30 VDC
- Impact strength: 4 kV
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 1 kg
Preferred areas of application
- Electric pumps and vacuum pumps
- Fans and fans
- Drilling cranes and extraction equipment
- Stirrers, centrifuges, saws and conveyors
- Machinery for working wood and metal, and grinding machines
Note:
When using IE3-Motoren, the higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices should generally be dimensioned to a higher power level.
The soft-starter VersiStart II [17 – 45 A] was developed for the controlled and low-wear start-up of three-phase induction motors. It reliably reduces starting current and torque, ensures a smooth run-up and thus extends the service life of the motor and drive. The device is microcontroller-controlled, compact and can be easily integrated into existing controllers thanks to pluggable power terminals.
Characteristics
- Two-phase controlled soft starter
- Microcontroller controlled
- Optimized soft start with torque reduction
- √3-Schaltung for more compact design
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization via three potentiometers (start-up time, start-up voltage, run-off time)
- No additional control voltage required
- no network center conductor (N) required
- spring-loaded terminals on the control side, power-side pluggable connections
- Cooling element temperature monitoring integrated
- Compact design: 45 mm to 32 A, 52,5 mm at 45 A
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operational mode, bridging and malfunction
Options
- Special voltages 230 V / 480 V
- Wide voltage 400–600 V with external control voltage 24 V DC (option B)
- Reporting contact (M): Start soft start to finish soft start
- Engine PTC monitoring (on request)
Technical data (excerpt)
- Mains voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 17 A / 25 A / 32 A / 45 A
- Engine power at 400 V: 7,5 – 22 kW
- Start-up time 0,5 – 10 s | Expiration time 0,5 – 10 s
- Starting voltage 40 – 80 %
- Relay output: 3 A / 250 VAC and 30 VDC
- Impact strength: 4 kV
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 1 kg
Preferred areas of application
- Electric pumps and vacuum pumps
- Fans and fans
- Drilling cranes and extraction equipment
- Stirrers, centrifuges, saws and conveyors
- Machinery for working wood and metal, and grinding machines
Note:
When using IE3-Motoren, the higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices should generally be dimensioned to a higher power level.
The soft starter VersiStart II [3,5 – 16 A] enables controlled, gentle start-up of asynchronous motors and significantly reduces mechanical and electrical loads. The device works microcontroller-controlled, compact and reliable – ideal for pumps, fans and conveyor technology. Thanks to its easy installation on the 35 mm standard rail, the VersiStart II is a cost-effective alternative to the classic star triangle switch.
Characteristics
- Two-phase soft starter
- Microcontroller controlled
- Optimized soft start with current and torque reduction
- Easy installation, for snapping on 35 mm standard rail
- Bridging relays integrated
- Parameterization over three potentiometers
- No additional control voltage required (standard)
- no network center conductor (N) required
- compact design, only 45 mm
- Low-cost replacement for star/triangle switches
- Degree of protection IP 20
Functions
- Soft start and soft exit
- Potential-free control input for start/stop
- three separately adjustable parameters: Start-up time, starting voltage, run-off time
- Boost start selectable
- Potential-free relay outputs for operating condition, bridging and failure (optional)
Options
- Special voltages 230 V / 480 V
- Wide Voltage 200 – 480 V with external control voltage 24 V DC (option B)
- Bypass and failure reporting contacts (option I)
- Engine PTC monitoring (option I)
- Current control function (200 – 500 % × I)N) (Option I)
- Cooling unit temperature monitoring (option I)
- √3-Schaltung for power optimization (Option I)
- Reporting contact ‘Soft start to soft exit’ (option M)
Technical data (excerpt)
- Operating voltage Ue: 400 V ± 10 % / 50–60 Hz
- Nominal equipment power: 3,5 A / 6,5 A / 12 A / 16 A
- Engine power at 400 V: 1,5 – 7,5 kW
- Start-up time 0,5 – 10 s | Expiration time 0,25 – 10 s
- Starting voltage 40 – 80 %
- Relay outputs switching power: 2 A / 250 VAC / 30 VDC
- Ambient temperature 0 – 45 °C / Bearing – 25 – 70 °C
- Weight approximately 0,4 kg
Preferred areas of application
- Door and door drives
- Pumps, fans and fans
- Conveying and packaging equipment
- Transportation equipment, assembly lines and mechanical engineering
Note:
When using IE3-Motoren, higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices each have a higher power level.
The soft starter SAS [3 – 11 kW] is a compact, single-phase controlled soft starter for the safe and uniform running up of three-phase and pole-switchable motors. It reduces mechanical loads during start-up, extends the service life of the drives and can be used universally in 230 V- and 400 V networks. Thanks to its simple parameterization and integrated bridging relays, the SAS series is ideal for compact controls and retrofit applications.
Characteristics
- single-phase soft starter
- Suitable for pole-switchable motors
- Switching from 400 V- to 230 V networks
- terminal arrangement suitable for switching installations
- for snapping onto 35 mm standard rail
- Bridging relays integrated
- no network center conductor (N) required
- Special voltages up to 640 V on request
- also suitable for single-phase applications
- Degree of protection IP 20
Functions
- Soft start with adjustable ramp
- two separately adjustable parameters: Start-up torque and start-up time
- Control input for pole-switchable motors
Options (on request)
- Potential-free input for control voltage 10 – 30 V DC
- SAS 3 – SAS 11 can be used as standard up to 480 V
- Special voltages 500 – 640 V (100 mm housing)
Technical data (excerpt)
- Mains voltage: 160 – 240 V ± 10 % (X1–X2 bridged) or 380 – 480 V ± 10 % (X1–X2 open)
- Nominal equipment power: 6,5 A / 12 A / 15 A / 25 A
- Engine power: 3 – 11 kW at 400 V
- System frequency: 50/60 Hz
- Start-up torque: 0 – 50 %
- Start-up time: 0,5 – 5 s
- maximum switching frequency: up to 240 /h (depending on type)
- maximum connection cross section: 2,5 mm²
- Ambient temperature: 0 – 45 °C / Warehouse –25 – 75 °C
- Weight: 0,3 – 0,5 kg
Preferred areas of application
- Door and door drives
- Packaging machinery
- Transport equipment
- Transformer or single-phase soft start systems
- Universal small drive applications
Note:
When using IE3-Motoren, higher starting and braking currents must be taken into account. We recommend that soft starters and brake devices should generally be dimensioned to a higher power level.