Protective circuit breakers
- Rated control supply voltage [Us]: 24–240 V AC, 50–400 Hz; 24–240 V DC Contacts: 1 NO + 1 NC
- Mounting: snaps onto DIN rail according to IEC/EN 60715 Ambient temperature: unencapsulated -25 to +60 °C; encapsulated -25 to +45 °C
- Degree of protection: IP20 Safe isolation according to EN 61140: 250 V AC between contacts; 250 V AC between contacts and supply voltage
-
Overvoltage category / pollution degree: category III / degree 3
- Rated operational current [Ie]: AC-15 at 240 V: 3 A; AC-14 at 300 V: 3 A and 400 V: 3 A; NO/NC at 300 V: 3 A and 380/400/415 V: 3 A (AC-14); NO/NC at 220/230/240 V: 3 A and 380/400/415 V: 1 A (AC-15)
- Conventional thermal current Ith: 6 A
- Power consumption: AC 3.5 VA; DC 2 W Trip/reset values: trip at ≥ 3600 Ω; reset at ≤ 1600 Ω
-
Maximum sensor cable length: 250 m, unshielded
- Dimensions (W × H × D): 23 × 84 × 104 mm
- Standards: IEC/EN 60947, VDE 0660, EN 55011
-
- Rated control voltage [Us]: 230 V AC, 50/60 Hz
- Contacts: 1 closer + 1 opener
- Assembly: Snap on top of top hat track to IEC/EN 60715
-
Ambient temperature:
- Open: –25 °C to +60 °C
- Encapsulated: –25 °C to +45 °C
- Degree of protection: IP20
-
Secure separation according to EN 61140:
- Between contacts: 250 V AC
- Between contacts and supply voltage: 250 V AC
- Overvoltage category / degree of contamination: Category III / Grade 3
-
Rated operating current [Ie]:
- Closers: 220–240 V AC: 3 A, 380–415 V AC: 1 A (AC-15)
- Openers: 220–240 V AC: 3 A, 380–415 V AC: 1 A (AC-15)
- Power consumption: 3,5 VA (AC operation only)
- Action and recurrence values: Trigger at ≥ 3600 Ω, restart at ≤ 1600 Ω
- Dimensions: (B x H x T) 23 x 84 x 104 mm
- Maximum line length to the sensor: 250 m
- Standards: IEC/EN 60947, VDE 0660, EN 55011
|
Designation |
Value |
|---|---|
| Rated voltage Un Rated voltage Un |
230 VAC / 400 VAC 230 VAC / 400 VAC |
| Rated frequency | Rated frequency | 50 Hz | 50 Hz |
| Rated residual current IΔn Rated residual current IΔn |
0,03 A; 0,3 A 0.03 A; 0.3 A |
| Tripping times Tripping times |
1× IΔn ≤ 300 ms; 5× IΔn ≤ 40 ms 1× IΔn ≤ 300 ms; 5× IΔn ≤ 40 ms |
| Response delay Response delay |
10 ms 10 ms |
| Surge current withstand capability Surge current resistance |
3 kA 3 kA |
| Rated impulse withstand voltage Rated surge voltage resistance |
4 kA 4 kA |
| Supply side | Feeding-in side | any | any desired |
| Operating range of the test device Range for test function |
2-pole: 30 mA - 150 - 250 V | 2 pole: 30 mA - 150 - 250 V 4-pole: 30 mA - 250 - 440 V | 4 pole: 30 mA - 250 - 440 V 4-pole: 300 mA - 200 - 440 V | 4 pole: 300 mA - 200 - 440 V |
| Number of poles | Number of poles | 2-pole / 4-pole | two pole / four pole |
| Lightning-resistant | lightning-proof | yes | yes |