TOSHIBA
- Engine power 0,25 kW
- Output in appearance 0,60 kVA
- Output current 1,4 A
- Dimensions WxHxD 72x130x102 m
- Output voltage 50... 330 V3AC depending on input voltage
- Output frequency 0,1... 400 Hz
- Input voltage 170... 264 V1AC ±10%
- input frequency 50... 60 Hz ±5%
- Overload 150% for 60 seconds
- Protection type IP20
- Ambient temperature -10...+60°C13
- Radio interference suppression filter IEC61800-3 C1 to 5 m, C2 to 10m motor line
- incl. PID; RS485 interface
- Engine power 0,55 kW
- Output current 2,4 A
- Dimensions WxHxD 72x130x121 mm
- Output voltage 50... 330 V3AC depending on input voltage
- Output frequency 0,1... 400 Hz
- Input voltage 170... 264 V1AC ±10%
- input frequency 50... 60 Hz ±5%
- Overload 150% for 60 seconds
- Protection type IP20
- Ambient temperature -10...+60°C13
- Radio interference suppression filter IEC61800-3 C1 to 5 m, C2 to 10m motor line
- Engine power 0,75 kW
- Output in appearance 1,80 kVA
- Output current 4,2 A
- Dimensions WxHxD 72x130x102 m
- Output voltage 50... 330 V3AC depending on input voltage
- Output frequency 0,1... 400 Hz
- Input voltage 170... 264 V1AC ±10%
- input frequency 50... 60 Hz ±5%
- Overload 150% for 60 seconds
- Protection type IP20
- Ambient temperature -10...+60°C13
- Radio interference suppression filter IEC61800-3 C1 to 5 m, C2 to 10m motor line
- incl. PID; RS485 interface
- Engine power 1,50 kW
- Output in appearance 3,00 kVA
- Output current 7,5 A
- Dimensions WxHxD 105x130x156 m
- Output voltage 50... 330 V3AC depending on input voltage
- Output frequency 0,1... 400 Hz
- Input voltage 170... 264 V1AC ±10%
- input frequency 50... 60 Hz ±5%
- Overload 150% for 60 seconds
- Protection type IP20
- Ambient temperature -10...+60°C13
- Radio interference suppression filter IEC61800-3 C1 to 5 m, C2 to 10m motor line
- incl. PID; RS485 interface
- Engine power 2,20 kW
- Output current 10,0 A
- Dimensions WxHxD 105x130x156 mm
- Output voltage 50... 330 V3AC depending on input voltage
- Output frequency 0,1... 400 Hz
- Input voltage 170... 264 V1AC ±10%
- input frequency 50... 60 Hz ±5%
- Overload 150% for 60 seconds
- Protection type IP20
- Ambient temperature -10...+60°C13
- Radio interference suppression filter IEC61800-3 C1 to 5 m, C2 to 10m motor line
- incl. PID; RS485 interface
The PDP002Z is a PROFIBUS-DP option card for communication between compatible Toshiba TOSVERT frequency inverters and a higher-level controller, for example a SPS. The frequency inverter can be integrated into an automation network as a PROFIBUS-DP slave via the module.
The module is particularly suitable for industrial applications in which drive data, control words, setpoint values, status words and actual values are to be transmitted via PROFIBUS. The PDP002Z supports PROFIBUS DP-V0 and the PROFIdrive profile for variable-speed drives.
Benefits
- PROFIBUS-DP communication module for Toshiba TOSVERT frequency inverter
- Integration of the frequency inverter as a PROFIBUS-DP slave
- Support for PROFIBUS DP-V0
- Support for PROFIdrive / Profile for Variable Speed Drives
- PPO Type 1 to 4 adjustable
- Station address adjustable via DIP switch
- Status display via LED for diagnosis and data exchange
- Automatic baud rate detection via the master configuration
Technical data
| Manufacturers | Toshiba and Toshiba Schneider Inverter Corporation |
| Type/Model | PDP002Z |
| Product type | PROFIBUS-DP Option Card / Communication Module |
| Communication protocol | PROFIBUS DP-V0 |
| Profile | PROFIdrive / Profile for Variable Speed Drives |
| PPO Type | 1 to 4 |
| Connection | D-Sub, 9-polig, female |
| Station address | Setting via DIP switch |
| baudrates | 9,6 kbit/s to 12 Mbit/s |
| Status indicators | ST LED for status / diagnosis, DX LED for data exchange |
| Operating temperature | -10 °C to +60 °C |
| Storage temperature | -25 °C to +65 °C |
| Relative humidity | 20 to 93 %, non-condensing |
| Vibration | max 5,9 m/s2, 10 to 55 Hz |
Compatibility
The PDP002Z is provided as a PROFIBUS-DP option for Toshiba TOSVERT VF-AS1 / VF-PS1 frequency inverters. Before ordering or installing, we recommend checking compatibility with the existing frequency inverter against the full type designation and the existing series of devices.
Installation instructions
- The installation and parameterisation shall be carried out only by qualified professionals.
- Before assembly or wiring, the frequency inverter must be switched voltage-free.
- After the switch-off, the discharge time of the frequency inverter must be observed.
- The PDP002Z does not have an integrated terminating resistor. When used at the bus end, a PROFIBUS connector with an activated termination resistor or a corresponding termination is required.
- After changing relevant communication parameters, a restart of the frequency inverter may be necessary.
Typical areas of application
- Connection of Toshiba frequency inverters to SPS systems
- Industrial drive automation with PROFIBUS-DP
- Transmission of control word, status word, setpoint values and actual values
- Retrofit or replacement of existing PROFIBUS-DP interface modules
Note: If spare parts are required, please compare the existing type designation of the frequency inverter and the designation of the previous option card. In case of uncertainty, you can send us a photo of the nameplate and the existing option card.