Skip to main content Skip to search Skip to navigation

DCEx 132 SAP/2 K – 5,5 kW – 230/400 V – B3 – IE3 – Explosion-protected three-phase motor

  • Type: DCEx 132 SAP/2 K
  • Motor design: Squirrel-cage induction motor
  • Rated power: 5,5 kW
  • Rated voltage / connection: 230 V Δ / 400 V Y
  • Mains frequency: 50 Hz
  • Poles: 2
  • Synchronous speed according to offer: 3.000 min⁻¹
  • Mounting: B3
  • Terminal box: on top
  • Explosion protection: II 2G Ex db eb IIC T4 Gb
  • Efficiency class: IE3
  • Protection rating: IP55
  • Thermal class: F
  • Cooling method: IC 411
  • Motor protection: 1 × 3 PTC
  • PTC response temperature according to report: 145 °C
  • Offered inverter frequency range: 10–50 Hz
  • Equipment: Additional nameplate for inverter operation
  • Motor frame size: 132
  • Shaft end: Ø 38 × 80 mm
  • B3 motor weight, approx.: 84 kg
  • Paint: RAL 7031 or as specified
  • Permissible ambient temperature according to report: −20 … +40 °C
  • Dimensional drawing: EX-132-B3 – DEx132… B3
  • B3 dimensions (L × W × H): 537 × 266 × 353 mm
  • Shaft height: 132 mm
  • Transverse foot-hole spacing: 216 mm
  • Longitudinal foot-hole spacings: 140 / 178 mm
  • Foot-hole diameter: 12 mm
  • Cable entries according to drawing: 2 × M32 × 1,5; 1 × M20 × 1,5
  • Shaft centre thread: DIN 332/2 – DM12
  • Technical clarification required: The supplied test report lists 1,470 rpm and 36 Nm despite the 2-pole design and 3,000 rpm synchronous speed in the offer. Rated speed, torque and associated electrical data have therefore not been accepted as confirmed. Mounting, connection dimensions, load data and suitability as a replacement for VEM K82R 132S2 must be checked before ordering.
  • Offered inverter range: 10–50 Hz with an additional nameplate. The finally confirmed inverter data and nameplate govern.
  • The general inverter table lists 15 Nm at 10–50 Hz with constant torque and 4.5 kW at 50 Hz for 132S/2. These series values require confirmation for DCEx 132 SAP/2 K.
  • operating instructions, sections 4.3–4.5, require temperature monitoring using thermal sensors and a separately certified tripping device for inverter operation.
  • Wiring diagram SVX2: PTC sensors on auxiliary terminals 12/13, maximum connection voltage 25 V. Observe the complete manufacturer instructions.