Temperature range: -25 °C/+110 °C *1. Flame resistant according to UL94V-2. 1) Continuous service temperature (according to IEC 60216), see material data sheet. Materials – contact carrier: PA, V-2 according to UL94; terminal body: CuZn, nickel underplated and tin-plated. Mechanical data – screw size: M3. Connectable conductors, screw-terminal connection. Stranded-conductor cross-section: 0,2–2,5 mm² (VDE), AWG 22–14 (CSA). Stranded conductor with ferrule: 0,2–1,5 mm² (VDE), AWG 24–16 (CSA). Solid-conductor cross-section: 0,2–2,5 mm² (VDE), AWG 22–14 (CSA). Stripping length: 7,0 ± 0,5 mm. Electrical data (at TU 20 °C). Rated current: 15 A (VDE, TU 100 °C). Rated voltage: 250 V AC (VDE)/300 V (B, CSA) *1. Insulation material group I (IEC)/0 (UL) (CTI = 600) *2. Creepage distance: 1,3 mm at maximum connected cross-section (solid conductor 2,5 mm²). Clearance: 1,3 mm at maximum connected cross-section (solid conductor 2,5 mm²). Insulation resistance > 10 GO. 1) according to IEC 60664/DIN EN 60664. 2) according to ANSI/UL 746A.