Skip to main content Skip to search Skip to navigation

EMV 480/340A 3F480-340.260CT

Enables conformity of the drive system to EN 55011, to IEC 61800-3
Typically C2 limits are met up to 50m
current 3x340 A; leakage current 42 mA; Loss 17 W @ 25°C
Rated voltage 520 Vrms (480 Vrms + 10%)
Frequency 50/60 Hz
Test voltage 2270 V DC, 2 s (L\L)
3000 V DC, 2 s (L\PE)
IEC Climate category 25/105/21
Ambient temperature + 45°C (max. 55°C, 1% current derating per degree)
installation height 1000 m (up to 2000 m 1% power reduction). per 100 m
Protection class IP20 ≤ 150A, IP00 ≥ 180A
connections 7... 150 A: Contact-protected screw terminals
180.. 2500 A: Power rails
Dimensions 340x230x140 mm

159,00 €
excl. 19% VAT , plus shipping costs
pcs