Skip to main content Skip to search Skip to navigation

SINUS I-PLUS Online IGBT frequency inverter SFC

Characteristics

  • With double transformer technology incl. isolating transformer
  • Transfolose monoblock high-performance plant
  • 3-Level IGBT inverter technology
  • Efficiency up to 95% in online operation
  • Low space requirement, small installation area
  • Power factor 1 at output (kVA=kW)
  • Colored touchscreen
  • Green Conversion Battery Care Technology
  • parallel switchbar of up to 6 identical systems for the purpose of increasing performance

Output

  • Power factor: Up to 1, without degradation of performance
  • Initial curve shape: Sinusoidal
  • Output voltage: 380...480 V3AC+N (max. Uin) fixed in the factory
  • Voltage tolerance: Static-symmetric ±1%, static-asymmetric ±2%, dynamic IEC/EN 62040-3 class 1 (20%-100%-20% ±5%)
  • Voltage control time: <20 ms
  • Output frequency: 60 or 50 Hz in the factory set ±0,1% (other frequencies possible on request)
  • phase angle fidelity: ±1° for all loads
  • THDv: <2,5% (lineare last), 5<% (nicht lineare Last) IEC EN 62040-3 wird voll eingehalten
  • Crest factor: 3:1 max. allowed without power reduction
  • Overload capability: 10 min >100…120%; 30 s 121…150%; 2 s 151…200%
  • Short-circuit behavior: Electronic protection circuit, power limited to 1,5 x In automatic off after 5 seconds

Receipt

  • Input voltage: 380...440 V3AC+N ±10% 3P+N
  • Input frequency: 50/60 Hz ±5%
  • Harmonics 3% THDi (at nominal load)

Other characteristics

  • Operating temperature: 0...+40°C - up to 55°C with Derating
  • Rel. Humidity: <95% (nicht kondensierend)
  • Operational altitude: <1000 m ü.M.
  • Noise level: <60 dB(A)
  • EMV: IEC 62040-2 (CE character)
  • Connection: Fixed connection on terminal, from the front bottom
  • Relay card with 8 potential-free switching contacts
  • Transportation option: Tractors/forklifts
  • Connections: external output switches; remotely operated emergency off;
  •  external switching to bypass; Contact for Diesel Generator Mode
  • Interfaces: RS232 + USB
  • Degree of protection: IP20 (on request IP54 possible)
Power | Rated output current | Short-circuit current 
Output voltage 
Output frequency 
Parallel Kit (up to 6 identical systems) 
ModBus Card (RS484 RTU protocol) 
SNMP/Web Adapter 
Contact for return protection 
Uninterrupted operation (batteries) 
Electroplating isolation transformer 
Price on request
  • Available